Function |
Measuring range |
Resolution |
Accuracy |
HVAC, Programmable HVAC |
Test voltage (AC)
Test current apparent capacitive resistive
Short circuit current
Output power |
0 … 1999 V
2.00 … 5.99 kV
0.0 … 99.9 mA
0.0 mA … 99.9 mA
-99.9 mA … 99.9 mA
> 200 mA
500 VAmax |
1 V
10 V
0.1 mA
0.1 mA
0.1 mA |
± (3 % of reading)
± (3 % of reading)
± (3 % of reading + 3 digits)
Indicative
Indicative |
HVDC, Programmable HVDC |
Test voltage (DC)
Test current |
0 ÷ 1999 V
2.00 ÷ 6.99 kV
0.01 ÷ 9.99 mA |
1 V
10 V
0.01 mA |
± (3 % of reading)
± (3 % of reading)
± (5 % of reading + 3 D) |
Discharging time |
t
Up |
0.0 ÷ 9.9 s
0 ÷ 550 V |
0.1 s
1 V |
± (5 % of reading + 3 D)
± (5 % of reading + 3 D) |
Continuity (0.2A, 4A, 10A, 25A) |
R |
0.00 Ω ÷ 19.99 Ω
20.0 Ω ÷ 99.9 Ω
100.0 Ω ÷ 199.9 Ω
200 Ω ÷ 999 Ω |
0.01Ω
0.1Ω
0.1Ω
1 Ω |
± (2 % of reading + 2 D)
± 3 % of reading
± 5 % of reading
Indicative |
Insulation resistance (250 V, 500 V, 1000 V), Insulation resistance – S (250 V, 500 V, 1000 V) |
Riso/Riso-s |
0.00 M Ω ÷ 19.99 M Ω
20.0 M Ω ÷ 199.9 M Ω |
0.01 M Ω
0.1 M Ω |
± (3 % of reading + 2 D)
± 5 % of reading |
Output voltage |
0 V ÷ 1200 V |
1 V |
±(3 % of reading + 2 D) |
Insulation resistance (50 V, 100 V), Insulation resistance – S (50 V, 100 V) |
Riso/Riso-s |
0.00 M Ω ÷ 19.99 M Ω
20.0 M Ω ÷ 199.9 M Ω |
0.01 M Ω
0.1 M Ω |
± (5 % of reading + 2 D)
± 20 % of reading |
Output voltage |
0 V ÷ 1200 V |
1 V |
±(3 % of reading + 2 D) |
(open circuit voltage <50 V a.c.) |
Isub / Isub s |
0.00 mA ÷ 19.99 mA |
10 μA |
± (5 % of reading + 3 D) |
Differential Leakage current |
Idiff |
0.00 mA ÷ 19.99 mA |
0.01 mA |
± (3 % of reading + 5 D) |
PE leakage current |
Ipe |
0.00 mA ÷ 19.99 mA |
0.01 mA |
± (3 % of reading + 3 D) |
Touch leakage current |
Itou |
0.00 mA ÷ 19.99 mA |
0.01 mA |
± (3 % of reading + 3 D) |
Power |
P |
0 W ÷ 999 W
1.00 kW ÷ 3.70 kW |
1 W
10 W |
± (5 % of reading + 5 D)
± 5 % of reading |
S |
0 VA ÷ 999 VA
1.00 kVA ÷ 3.70 kVA |
1 VA
10 VA |
± (5 % of reading + 5 D)
± 5 % of reading |
Q |
±(0 ÷ 999) VAr
±(1.00 ÷ 3.70) kVAr |
1 VAr
10 VAr |
± (5 % of reading + 5 D) |
PF |
0.00i ÷ 1.00i
0.00c ÷ 1.00c |
0.01
0.01 |
± (5 % of reading + 5 D)
± (5 % of reading + 5 D) |
THDU |
0.0% ÷ 99.9% |
0.1% |
±(5 % of reading + 5 D) |
THDI |
0.0% ÷ 99.9% |
0.1% |
±(5 % of reading + 5 D) |
Cos Phi |
0.00i ÷ 1.00i
0.00c ÷ 1.00c |
0.01
0.01 |
±(5 % of reading + 5 D)
±(5 % of reading + 5 D) |
U |
0.1 V ÷ 199.9 V
200 V ÷ 264 V |
0.1
1 V |
±(3 % of reading + 10 D)
±(3 % of reading) |
I |
0.00 A ÷ 16.00 A |
0.01 |
±(3 % of reading + 5 D) |
Power supply |
110 V / 230 V AC, 50 Hz / 60 Hz |
Overvoltage category |
CAT II / 300 V, CAT II / 600 V (DISCH1 / DISCH2, only) |
Protection class |
I |
HV output |
5 kV a.c. / 6 kV d.c., double insulation |
COM port |
4 x RS232, 1 x USB, 1 x Ethernet, 1 x Bluetooth |
Dimensions (w×h×d): |
43,5 cm x 29,2 cm x 15,5 cm |
Weight: |
17 kg |